Aluminum SER

Aluminum SER                     

 DOWNLOAD ALUMINUM SER PDF

 

Applications Top of Page


May be used as service-entrance conductors and in other applications where SE cables are permitted when installed as specified by NEC® Article 230. May be used in dry, above-ground applications only at temperatures up to 90°C.

Insulated Phase Conductors and Neutral Top of Page

Compact stranded AA-8000 Series aluminum alloy
Type XHHW-2 conductors
Black XLP (cross-linked polyethylene), rated to 90°C in wet or dry locations
One phase conductor has a red stripe on its insulation surface for easy polarity identification

Bare Equipment Grounding Conductor Top of Page


Compact stranded AA-8000 Series aluminum alloy 

Assembly Top of Page

Insulated and bare conductors are twisted together.
A glass-reinforced tape is applied over the conductors. 

Jacket Top of Page

Gray, sunlight-resistant PVC (polyvinyl chloride) jacket over the complete assembly

Industry Standards Top of Page

UL® 44 (insulated conductors)
UL® 854 Service Entrance Cables
Federal Specification A-A-59544
NFPA70: National Electrical Code®
RoHS Compliant

Surface Print Top of Page


Sample: AA-8000 AL TYPE SE CABLE STYLE R XHHW-2
600V 3 CDRS. 2 AWG 1 CDR. 4 AWG (UL)

 

 

         
Product Code Number

Conductors

Bare Equipment Ground AWGApprox. O.D. InchesAllowable Ampacities*

    Approx.     Net Wt. Lbs/M Ft.

UPC Code

AWG Size  75°C   ***   90°C   ****Dwelling *****
         
 536-3600J  6-6-6 60.650 40 50 55182662927584553

 536-4800J 

 2-2-2 40.863 75 90 100346 662927584706 
536-5600J1/0-1/0-1/021.061100120135526662927584805
536-6000J2/0-2/0-2/011.164115135150637662927584850
536-6800J4/0-4/0-4/02/01.390150180205948662927584959
536-7000J250-250-2503/01.6011702052301106662927585703
         

* Per Table 310-16 NEC®
** For termination to equipment for circuits rated 100 amperes or less or marked for
Nos. 6 through 1 conductors.
*** For termination to equipment for circuits rated over 100 amperes or marked for
conductors larger than No. 1.
**** Dry locations.
***** For dwelling units, conductors shall be permitted at listed ampacities for 120/240 volt, 3 wire, single-phase service conductors that supply the total load.

 

 

  
Package CodeJ
AWG Size500 FT
Reel
  
6-6-6-6X
2-2-2-4X
1/0-1/0-1/0-2X
2/0-2/0-2/0-1X
4/0-4/0-4/0-2/0X
250-250-250-3/0X