Aluminum SER
| DOWNLOAD ALUMINUM SER PDF |

| Applications | Top of Page |
May be used as service-entrance conductors and in other applications where SE cables are permitted when installed as specified by NEC® Article 230. May be used in dry, above-ground applications only at temperatures up to 90°C.
| Insulated Phase Conductors and Neutral | Top of Page |
Compact stranded AA-8000 Series aluminum alloy
Type XHHW-2 conductors
Black XLP (cross-linked polyethylene), rated to 90°C in wet or dry locations
One phase conductor has a red stripe on its insulation surface for easy polarity identification
| Bare Equipment Grounding Conductor | Top of Page |
Compact stranded AA-8000 Series aluminum alloy
| Assembly | Top of Page |
Insulated and bare conductors are twisted together.
A glass-reinforced tape is applied over the conductors.
| Jacket | Top of Page |
Gray, sunlight-resistant PVC (polyvinyl chloride) jacket over the complete assembly
| Industry Standards | Top of Page |
UL® 44 (insulated conductors)
UL® 854 Service Entrance Cables
Federal Specification A-A-59544
NFPA70: National Electrical Code®
RoHS Compliant
| Surface Print | Top of Page |
Sample: AA-8000 AL TYPE SE CABLE STYLE R XHHW-2
600V 3 CDRS. 2 AWG 1 CDR. 4 AWG (UL)
| Product Code Number | Conductors | Bare Equipment Ground AWG | Approx. O.D. Inches | Allowable Ampacities* | Approx. Net Wt. Lbs/M Ft. | UPC Code | ||
|---|---|---|---|---|---|---|---|---|
| AWG Size | 75°C *** | 90°C **** | Dwelling ***** | |||||
| 536-3600J | 6-6-6-6 | 6 | 0.650 | 40 | 50 | 55 | 182 | 662927584553 |
536-4800J | 2-2-2-4 | 4 | 0.863 | 75 | 90 | 100 | 346 | 662927584706 |
| 536-5200J | 1-1-1-3 | 3 | 0.986 | 100 | 115 | 110 | 449 | 662927584751 |
| 536-5600J | 1/0-1/0-1/0-2 | 2 | 1.061 | 100 | 120 | 135 | 526 | 662927584805 |
| 536-6000J | 2/0-2/0-2/0-1 | 1 | 1.164 | 115 | 135 | 150 | 637 | 662927584850 |
| 536-6800T | 4/0-4/0-4/0-2/0 | 2/0 | 1.390 | 150 | 180 | 205 | 948 | 662927584973 |
| 536-6800J | 4/0-4/0-4/0-2/0 | 2/0 | 1.390 | 150 | 180 | 205 | 948 | 662927584959 |
* Per Table 310-16 NEC®
** For termination to equipment for circuits rated 100 amperes or less or marked for
Nos. 6 through 1 conductors.
*** For termination to equipment for circuits rated over 100 amperes or marked for
conductors larger than No. 1.
**** Dry locations.
***** For dwelling units, conductors shall be permitted at listed ampacities for 120/240 volt, 3 wire, single-phase service conductors that supply the total load.
| Package Code | T | J |
|---|---|---|
| AWG Size | 250 FT Reel | 500 FT Reel |
| 6-6-6-6 | X | |
| 2-2-2-4 | X | |
| 1-1-1-3 | X | |
| 1/0-1/0-1/0-2 | X | |
| 2/0-2/0-2/0-1 | X | |
| 4/0-4/0-4/0-2/0 | X | X |