Copper XHHW-2

Copper XHHW-2                         

DOWNLOAD COPPER XHHW-2 PDF

 

Applications Top of Page


For use in conduit or other recognized raceways for service, feeder, and branch circuit
applications as specified in the NEC®. Good choice for industrial applications where
better insulation toughness and resistance to moisture and heat are desired. For use in
wet or dry locations at temperatures up to 90°C. Sunlight-resistant.

Conductors Top of Page

Stranded conductors: Uncoated, soft copper per ASTM-B8 (2 AWG and 250 MCM-600
MCM), and ASTM-B787 (1 AWG-4/0)  

Insulation Top of Page


XLP (cross-linked polyethylene)  

Industry Standards Top of Page

UL 44 – File No. E63539
CSA LL 82214
ASTM-B3
ASTM-B8
ASTM-B787
Federal Specification A-A-59544
NFPA70: National Electrical Code®
NEMA WC70/ICEA S-95-658

Surface Print Top of Page

Sample: 2 AWG XHHW-2 600V SUN-RES GASOLINE & OIL RESISTANT I & II
(UL) E63539/XLPE RW90 (-40 °C) CSA LL 82214

  

          
Product Code Number ConductorsInsulation Thickness Mils.Approx. O.D. InchesAllowable AmpacitiesApprox. Net Wt. Lbs./M Ft.

UPC Code

AWG SizeNo. of Strands60°C**75°C***90°C****
          
117-4000K87450.24040505565048243240517
 117-4000P 87450.24040505565048243240531
117-4200K67450.28055657597 048243241019 
117-4200P67450.28055657597048243241033
117-4400K47450.330708595148 048243241514 
117-4400P47450.330708595148 048243241538 
117-4500K37450.353--110180 048243241712 
117-4500P37450.353--110180 048243241736 
117-4600K27450.39095115130 229 048243241811 
117-4600P27450.39095115130229 048243241835 
117-4700K119550.450110130150293 048243242016 
117-4700P119550.450110130150293 048243242030 
 117-5000K 1/019550.489125150170364 048243242269 
117-5000P1/019550.489125150170364 048243246427 
117-5200K 2/019550.530145175195449 048243242313 
117-5200P2/019550.530145175195449 048243242344 
117-5400K3/019550.550165200225559 048243242368 
117-5400P3/019550.550165200225559048243242382
117-5600K4/019550.640195230260698 048243242412 
117-5600P4/019550.640195230260698 048243242443 
117-6000K 250 37650.710215255290834 048243242467 
117-6000M 250 37650.710215255290834 048243242498 
117-6400M300 37650.760240285320995 048243242528 
117-6800K350 37650.8202603103501152 048243242566 
117-6800M35037650.8202603103501152048243242542
117-7200K40037650.8602803353801309048243242610
117-7200R40037650.8602803353801309 048243242764 
117-8000K50037650.9503203804301622 048243242672 
117-8000M500

37

650.9503203804301622 048243242689 
117-8400K60061801.0403554204751947048243242719
117-8400R60061801.0403554204751947048243242733
          

 ** Per Table 310-16 NEC®
*** For termination to equipment for circuits rated 100 amperes or less or marked for size 14 through 1 AWG conductors.
**** For termination to equipment for circuits rated over 100 amperes or marked for conductors larger than 1 AWG.
**** For use in wet or dry locations.

 

     
Package CodeKRMP
AWG Size
1,000' Reel2,000' Reel2,500' Reel5,000' Reel
     
8 StrandedX  X
6 StrandedX  X
4 StrandedX  X
3 StrandedX  X
2 StrandedX  X
1 StrandedX  X
1/0X  X
2/0X  X
3/0X  X
4/0X  X
250 MCMX X 
350 MCMX X 
400 MCMXX  
500 MCMX X 
600 MCMXX