|
APPLICATIONS • May be used as service-entrance conductors and in other applications where SE cables are permitted when installed as specified by NEC® Article 230 • May be used in wet or dry locations at temperatures up to 90°C
CONDUCTORS • Stranded conductors: Uncoated copper per ASTM-B3, ASTM-B8 and ASTM-B787
PHASE CONDUCTORS • Type THHN conductors • Black PVC (polyvinyl choloride), rated 90°C dry or wet, jacketed with black nylon (polyaide) • One of the phase conductors has a red stripe on the surface of the insulation for polarity identification NEUTRAL CONDUCTOR • White PVC (polyvinyl chloride), rated 90 C jacketed with white nylon (polyamide)
EQUIPMENT GROUND CONDUCTOR • Bare stranded copper conductor
ASSEMBLY • The insulated and bare conductors are twisted together • A glass-reinforced tape is applied over the conductors
JACKET • A gray, sunlight resistant PVC (polyvinyl chloride) jacket is applied over the complete assembly
INDUSTRY STANDARDS • UL 83 (insulated conductors) • UL 854 Service Entrance Cables, File No. 11098 • ASTM - B3 • ASTM - B8 • ASTM - B787 • Federal Specification A-A-59544 • NFPA70: National Electrical Code®
SURFACE PRINT • Sample: TYPE SE CABLE STYLE R TYPE THHN OR THWN CDRS 3 CDRS 6 AWG 1 CDR 6 AWG 600V E11098-A (UL)
|
|
|
Product Code Number
|
Stranding
|
Size/Construction AWG
|
Approx. O.D. Inches
|
Allowable Ampacities*
|
Approx. Net Wt. lbs./m ft.
|
|
Phase Conductor & Neutral
|
Equipment Grounding Conductor
|
60°C **
|
75°C ***
|
90°C ****
|
Dwelling *****
|
|
136-3600
|
7 |
7
|
6-6-6-6
|
660
|
55
|
65
|
75
|
-
|
411
|
|
136-4000
|
7
|
7
|
4-4-4-6
|
800
|
70
|
85
|
95
|
100
|
595
|
|
136-4400
|
7
|
7
|
3-3-3-5
|
905
|
85
|
100
|
110
|
110
|
738
|
|
136-4800
|
7
|
7
|
2-2-2-4
|
970
|
95
|
115
|
130
|
125
|
899
|
|
136-5200
|
19
|
7
|
1-1-1-3
|
1125
|
110
|
130
|
150
|
150
|
1140
|
| 136-6000 |
19 |
19 |
2/0-2/0-2/0-1 |
1250 |
145 |
175 |
195 |
200 |
1772 |
| * |
Per Table 310-16 NEC® |
| ** |
For termination to equipment for circuits rated 100 amperes or less or marked for Nos. 14 AWG through 1 AWG conductors. See Art. 110.13 (C) (1) NEC®. |
| *** |
For termination to equipment for circuits rated 100 amperes or marked for conductors larger than No. 1 AWG. See Art. 110.13 (C) (1) NEC®. |
| **** |
Dry or wet locations, for ampacity derating purposes. |
| ***** |
For dwelling units, conductors shall be permitted at listed ampacities for 120/240 volt, 3 wire, single-phase service conductors that supply the total load. Per Table 310-15(B) (6) NEC®. |
|
|
Package Code
|
J
|
|
AWG Size
|
500' spool or reel
|
|
6-6-6-6 Stranded
|
X
|
|
4-4-4-6 Stranded
|
X
|
|
3-3-3-5 Stranded
|
X
|
|
2-2-2-4 Stranded
|
X
|
|
1-1-1-3 Stranded
|
X
|
|
2/0-2/0-2/0-1 Stranded
|
X
|
|
|
|