PRODUCTS - COPPER SER

Type SE, Style SER
Service Entrance
THHN Copper Conductors/PVC Jacket
90°C Dry or Wet
600 Volts
Download PDF
 

APPLICATIONS
• May be used as service-entrance conductors and in other
  applications where SE cables are permitted when installed as
  specified by NEC® Article 230
• May be used in wet or dry locations at temperatures up to 90°C

CONDUCTORS
• Stranded conductors: Uncoated copper per ASTM-B3, ASTM-B8
  and ASTM-B787

PHASE CONDUCTORS
• Type THHN conductors
• Black PVC (polyvinyl choloride), rated 90°C dry or wet, jacketed
  with black nylon (polyaide)
• One of the phase conductors has a red stripe on the surface of
  the insulation for polarity identification
 
NEUTRAL CONDUCTOR
• White PVC (polyvinyl chloride), rated 90 C jacketed with white
  nylon (polyamide)

EQUIPMENT GROUND CONDUCTOR
• Bare stranded copper conductor

ASSEMBLY
• The insulated and bare conductors are twisted together
• A glass-reinforced tape is applied over the conductors

JACKET
• A gray, sunlight resistant PVC (polyvinyl chloride) jacket is applied
  over the complete assembly

INDUSTRY STANDARDS
• UL 83 (insulated conductors)
• UL 854 Service Entrance Cables, File No. 11098
• ASTM - B3
• ASTM - B8
• ASTM - B787
• Federal Specification A-A-59544
• NFPA70: National Electrical Code®

SURFACE PRINT
• Sample: TYPE SE CABLE STYLE   R TYPE THHN OR THWN 
  CDRS 3 CDRS 6 AWG 1 CDR 6 AWG 600V E11098-A (UL)

 
Product Code Number
Stranding
Size/Construction AWG
Approx. O.D. Inches
Allowable Ampacities*
Approx. Net Wt. lbs./m ft.
Phase Conductor & Neutral
Equipment Grounding Conductor
60°C
**
75°C
***
90°C
****
Dwelling
*****
136-3600
7
7
6-6-6-6
660
55
65
75
-
411
136-4000
7
7
4-4-4-6
800
70
85
95
100
595
136-4400
7
7
3-3-3-5
905
85
100
110
110
738
136-4800
7
7
2-2-2-4
970
95
115
130
125
899
136-5200
19
7
1-1-1-3
1125
110
130
150
150
1140
136-6000 19 19 2/0-2/0-2/0-1 1250 145 175 195 200 1772
* Per Table 310-16 NEC®
** For termination to equipment for circuits rated 100 amperes or less or marked for Nos. 14 AWG through 1 AWG conductors.  See Art. 110.13 (C) (1) NEC®.
*** For termination to equipment for circuits rated 100 amperes or marked for conductors larger than No. 1 AWG.  See Art. 110.13 (C) (1) NEC®.
**** Dry or wet locations, for ampacity derating purposes.
***** For dwelling units, conductors shall be permitted at listed ampacities for 120/240 volt, 3 wire, single-phase service conductors that supply the total load. Per Table 310-15(B) (6) NEC®.

 

Package Code
J
AWG Size
500' spool or reel
6-6-6-6 Stranded
X
4-4-4-6 Stranded
X
3-3-3-5 Stranded
X
2-2-2-4 Stranded
X
1-1-1-3 Stranded
X
2/0-2/0-2/0-1 Stranded
X