Type SE, Style SER
Service XHHW-2 Insulated
XLP Aluminum Conductors/PVC Jacket
90°C Dry or Wet
600 Volts
Download PDF
 

APPLICATIONS
• May be used as service-entrance conductors and in other
  applications where SE cables are permitted when
  installed as specified by NEC® Article 230
• May be used in wet or dry locations at temperatures up to
  90°C

INSULATED PHASE CONDUCTORS AND NEUTRAL
• Compact stranded AA-8000 Series aluminum alloy
• Type XHHW-2 conductors
• Black XLP (cross-linked polyethylene), rated 90°C wet or
  dry locations
• One of the phase conductors has a red stripe on the
  surface of the insulation for polarity identification
• The complete surface of the neutral conductor is painted
   white

BARE EQUIPMENT GROUNDING CONDUCTOR
• Compact stranded AA-8000 Series aluminum alloy

ASSEMBLY
• The insulated and bare conductors are twisted together
• A glass-reinforced tape is applied over the conductors

JACKET
• A gray, sunlight resistant PVC (polyvinyl chloride) jacket is
  applied over the complete assembly

INDUSTRY STANDARDS
• UL 44 (insulated conductors)
• UL 854 Service Entrance Cables
• Federal Specification A-A-59544
• National Electrical Code®

SURFACE PRINT
• Sample: AA-8000 AL TYPE SE CABLE STYLE R XHHW-2
  600V 3 CDRS. 2 AWG 1 CDR. 4 AWG (UL)

 
Product
Code
Number
Insulated Conductors
Bare
Equipment
Ground
AWG
Approx.
O.D.
Inches
Allowable Ampacities*
Approx.
Net Wt.
 lbs./m ft.
AWG Size
No. of
Strands
60°C
**
75°C
***
90°C
****
Dwelling
*****
536-3600
6-6-6
7
6
0.650
40
50
60
-
182
536-4800
2-2-2
7
4
0.863
75
90
100
100
346
536-5600
1/0-1/0-1/0
19
2
1.061
100
120
135
125
526
536-6000
2/0-2/0-2/0
19
1
1.164
115
135
150
150
637
536-6800
4/0-4/0-4/0
19
2/0
1.390
150
180
205
200
948
* Per Table 310-16 NEC®
** For termination to equipment for circuits rated 100 amperes or less or marked for Nos. 14 through 1 conductors.
*** For termination to equipment for circuits rated 100 amperes or marked for conductors larger than No. 1.
**** Wet or dry locations.
***** For dwelling units, conductors shall be permitted at listed ampacities for 120/240 volt, 3 wire, single-phase service conductors that supply the total load.