USE-2

USE-2                        

DOWNLOAD USE-2 PDF

 

Applications Top of Page

 

For use in conduit or suitable for use as underground service entrance cable for direct burial per NEC®. Good choice for industrial applications where better insulation toughness and resistance to moisture and heat are desired. For use as RHH or RHW-2 in wet or dry locations at temperatures up to 90°C. Sunlight-resistant. For CT use on 1/0 and larger.

 

  

Conductors Top of Page

Stranded conductors: Uncoated, soft copper per ASTM-B3, ASTM-B8 (12 AWG-2 AWG and 250 MCM-500 MCM), and ASTM-B787 (1 AWG-4/0)

 

 

Insulation Top of Page

 XLP (cross-linked polyethylene)

 

 

Industry Standards Top of Page

UL 44 (RHH or RHW-2)
UL 854 (USE-2), File No. E63541
ASTM-B3
ASTM-B8
ASTM-B787
Federal Specification A-A-59544
NFPA70: National Electrical Code®
NEMA WC70/ICEA S-95-658

 

 

Surface Print Top of Page

Sample: 2 AWG XLP TYPE RHH OR RHW-2 OR USE-2 600V SUN RES GASOLINE & OIL RESISTANT I & II (UL) E63541

  

         
Product
Code
Number
ConductorsInsulation
Thickness
Mils.
Approx.
O.D.
Inches
Allowable AmpacitiesApprox.
Net Wt.
Lbs./M Ft.
AWG
Size
No. of
Strands
60°C
**
75°C
***
90°C
****
         
1201-24XX147450.16015151521
1201-26XX127450.18020202029
1201-28XX107450.20030303042
1201-40XX8760 0.280 40 50 55 65
1201-42XX67600.320 55 65 75 102
1201-44XX4760 0.370 70 85 95 154
1201-45XX37600.40085100115192
1201-46XX2760 0.430 95 115 130 236
1201-47XX11980 0.500 110 130 150 307
1201-50XX1/01980 0.540 125 150 170 379
1201-52XX2/01980 0.590 145 175 195 466
1201-54XX3/01980 0.640 165 200 225 580
1201-56XX4/01980 0.700 195 230 260 719
1201-60XX2503795 0.780 215 255 290 861
1201-64XX30037950.8402402853201015
1201-68XX3503795 0.880 260 310 350 1183
1201-80XX5003795 1.010 320 380 430 1658
1201-84XX600611101.1003554204752000
1201-86XX750611101.2004004755352479
         

XX Color add code is as follows: Black - 01, White - 02, Red - 03, Blue - 04, Green - 05, Orange - 06, Yellow - 07, Brown - 08, Gray - 10.

  * Per Table 310-16 NEC®
** For termination to equipment for circuits rated 100 amperes or less or marked for Nos. 14 through 1 conductors.
*** For termination to equipment for circuits rated over 100 amperes or marked for conductors larger than No. 1.
**** RHH in dry locations. RHW-2 and USE-2 in wet or dry locations.

 

       
Package CodeJKLRMP
AWG Size500' Spool1,000' Reel1,000' Reel2,000' Reel2,500' Reel5,000' Reel
       
14 StrandedX   X 
12 StrandedX   X 
10 StrandedX   X 
8 Stranded X    X
6 Stranded X    X
4 Stranded X   X
3 Stranded X   X
2 Stranded X   X
1 Stranded X   X
1/0 X   X
2/0 X   X
3/0 X   X
4/0 X   X
250 MCM X  X 
300 MCM X  X 
350 MCM X  X  
500 MCM X  X 
600 MCM X X  
750 MCM XX