NMB

NMB                           

DOWNLOAD NMB PDF

 

Applications Top of Page

 

For use primarily in residential wiring, including branch circuits for outlets, switches, etc. May be
installed in both exposed and concealed work in normally dry locations. May be installed in air
voids of masonry block or tile walls where these walls are not subject to excessive moisture or
dampness. May be installed in locations with temperatures up to 90°C, but with the
ampacity limited to that of 60°C conductors. Added Circuit: For use primarily in residential wiring
for branch circuits supplying outlets located in bedrooms and other areas. Has two separated
neutrals so one cable can be used to run two circuits when sharing of a neutral is not allowed.

 

Conductors Top of Page

Solid conductors: Soft, uncoated copper per ASTM-B3

Stranded conductors: Uncoated copper per ASTM-B3 and ASTM B8

  

Conductor Insulation and Jacket Top of Page

  

Color-coded PVC (polyvinyl chloride), rated 90°C dry with clear nylon (polyamide).
Added Circuit: Color-coded PVC rated 90°C: black, white, red and white with red stripe. Insulated
conductors also jacketed with clear nylon (polyamide).

 

Grounding Conductor Top of Page
 

Soft, uncoated copper per ASTM-B3

 

Assembly Top of Page

Two-conductor constructions have the insulated conductors laid parallel. Ground
wire is wrapped with paper and laid parallel between the insulated conductors. The
entire construction is wrapped with a paper separator before applying the jacket. Three
-conductor constructions have the insulated conductors twisted together or laid parallel to each
other. Ground wire is wrapped with paper and twisted together or laid parallel to the insulated
conductor.

Jacket Top of Page

30 mil-thick PVC (polyvinyl chloride) jacket applied over the complete assembly
14-2, 14-2-2 & 14-3 w/ground: white
12-2, 12-2-2 & 12-3 w/ground: yellow
10-2 & 10-3 w/ground: orange
8 AWG or larger: black

Industry Standards Top of Page

UL 83 File # E15119
UL 719 Non-Metallic Sheathed Cable File #E9810
ASTM-B3
ASTM-B8
Fed. Spec. A-A-59544
NFPA70: NEC®
RoHS Compliant

*It is the sole responsibility of the end user to determine suitability of this product for its intended end use and application.

Surface Print Top of Page

Sample: NM-B 14-2 W/G 600V Cirtex-A (UL)

        
Product Code
Number &
Package Code
W/ Ground
ConductorsGround
Wire
AWG
Insulation
& Nylon
Thickness
Mils.
Cable
Dimension
Mils.
Ampacity
at 30°C
per NEC*
Approx. Net
Wt. Lbs./M Ft.
AWG &
No. Cond.
No. of
Strands
147
W/ Ground
        
147-1402A314-2Solid1419.185 x .3701558
147-1403A314-3Solid1419.4951576
147-1662F12-2Solid1219.200 x .4002082
147-1862G10-2Solid1024.225 x .49030125

147-4002D

8-27 10 35.320 x .68040204
147-4202D6-271035.350 x .71055276
 147-1463G14-3Solid 1419.4951576
147-1464G14-2-2Solid1419.52015133
147-1602A3  12-2Solid1219.200 x .4002082
 147-1603AR 12-3Solid1219.52020108
147-1664G 12-2-2Solid1219.5353093
147-1803A3 10-3Solid1024.53530164
147-4003A8-371035.72540250
147-4403J4-37846.105070556
147-4603J2-37846.119595823
        

 

      

PACKAGE CODE

D

125' Coil

G

250' Coil

J

500' Coil

K

1,000' Reel

P

5,000' Reel

14-2 Solid (147-1402)   X 
14-2 Solid (147-1462) XX  
12-2 Solid (147-1602)   X 
12-2 Solid (147-1662) XX  
10-2 Solid (147-1802)  XX 
10-2 Solid (147-1862) X   
8-2 Stranded (147-4002)X XX 
6-2 Stranded (147-4202)X XX 
14-3 Solid (147-1403)   X 
14-3 Solid (147-1463) XX  
12-3 Solid (147-1603)   X 
12-3 Solid (147-1663) X   
10-3 Solid (147-1803)   XX 
10-3 Solid (147-1863) X   
8-3 Stranded (147-4003)XXXX 
6-3 Stranded (147-4203)X XXX
4-3 Stranded (147-4403)  XX 
2-3 Stranded (147-4603)  X  
14-2-2 Solid (147-1464) X   
12-2-2 Solid (147-1664) X