Aluminum SEU

Aluminum SEU                

DOWNLOAD ALUMINUM SEU PDF

 

Applications Top of Page

 
May be used as service-entrance conductors when installed as required by NEC®
Article 230. May be used for branch circuits or feeders within a building as specified by
the NEC Section 338-10.

Conductors Top of Page

 Compact stranded AA-8000 Series aluminum alloy 

Conductor Insulation Top of Page


Type XHHW-2 conductors
Black XLP (cross-linked polyethylene), rated 90°C in wet or dry locations
Polarity ID: A red stripe on one conductor’s insulation surface 

Grounding Conductor Top of Page

 
Bare conductor strands are helically wound around two paralleled insulated conductors. 

Assembly Top of Page


Glass-reinforced tape applied over conductors 

Jacket Top of Page

 
Gray, sunlight-resistant PVC (polyvinyl chloride) over entire assembly 

Industry Standards Top of Page

UL Standard 44 (Insulated Conductors)
UL 854 Service Entrance Cables
Federal Specification A-A-59544
NFPA70: National Electrical Code®  

Surface Print Top of Page

 
Sample: AA-8000 AL TYPE SE CABLE STYLE U XHHW-2 660V 2 CDRS 2 AWG 1 CDR
4AWG (UL)


 

Product Code Number
2 CONDUCTORS
AWG
Concentric AWG
Approx O.D. Inches
Allowable Ampacities*
Approx. Net Wt. lbs./m ft.
UPC Code
60°C
**
75°C
***
90°C
****
Dwelling
*****
530-3600J
6-6
6
.458 x .720
40
50
60
-
143
662927580418
 530-3600T6-66 .458 x .720405060-143048243580439
 530-4600J2-24 .559 x .9197590100100259662927580661
530-4800J
2-2
2
.559 x .919
75
90
100
100
282
662927580715
530-5200J1/0-1/01/0.680 x 1.125100120135135428662927580814
530-6000J2/0-2/02/0.736 x 1.221115135150150514662927580913
530-6600J
4/0-4/0
2/0
.818 x 1.406
150
180
205
200
692
662927581064
530-6800G4/0-4/04/0.857 x 1.445150180205200762662927581125
530-6800J
4/0-4/0
4/0
.857 x 1.445
150
180
205
200
762
662927581118
 
*Per Table 310-16 NEC®
**For termination to equipment for circuits rated 100 amperes or less or marked for Nos. 14 through 1 conductors.
***For termination to equipment for circuits rated 100 amperes or marked for conductors larger than No. 1.
****Wet or dry locations.
*****For dwelling units, conductors shall be permitted at listed ampacities for 120/240 volt, 3 wire, single-phase service conductors that supply the total load.
Package Code
G
J
T
AWG Size
250' reel
500' reel
250' reel
6-6-6
 
X
X
2-2-2
 
X
 
2-2-4 X 
1/0-1/0-1/0 
X
 
2/0-2/0-2/0  X 
4/0-4/0-2/0 X 
4/0-4/0-4/0
X
X