Copper SEU

Copper SEU                      

DOWNLOAD COPPER SEU PDF

 

Applications Top of Page

May be used as service-entrance conductors when installed as required by NEC® Article 230. May be used for branch circuits or feeders within a building as specified by the NEC Section 338-10. 

Conductors Top of Page

 Stranded conductors: uncoated copper per ASTM-B3, ASTM-B8, and ASTM-B787

Insulated Conductors Top of Page


Type THHN conductors
Black PVC (polyvinyl chloride), rated 90°C in wet or dry locations
Jacketed with black nylon (polyamide)
Polarity ID: A red stripe on one conductor's insulation surface 

Neutral Conductor Top of Page

 Stranded, uncoated copper per ASTM-B3, ASTM-B8, and ASTM-B787

Assembly Top of Page

Parallel-laid conductors with the neutral conductor between the two insulated conductors. Conductors are wrapped with a fiberglass-reinforced polyester tape. 

Jacket Top of Page

 Gray, sunlight-resistant PVC (polyvinyl chloride) over entire assembly 

Industry Standards Top of Page

UL 83 (Insulated Conductors)
UL 854 Service Entrance Cables, FILE NO. 11098
ASTM-B3
ASTM-B8
ASTM-B787
Federal Specification A-A-59544
NFPA70: National Electrical Code® 

Surface Print Top of Page

 Sample: TYPE SE CABLE STYLE U TYPE THHN OR THWN CDRS 2 CDRS? 6 AWG 1 CDR 8 AWG 600V E11098-A (UL) 

  

            
Product
Code
Number
2 ConductorsBare NeutralApprox.
O.D.
Strands
Allowable Ampacities*Approx.
Net Wt.
Lbs./M Ft.
UPC
Code
 AWG
Size
No. of
Strands
AWG
Size
No. of
Strands
60°C
**
75°C
***
90°C
****
Dwelling
*****
            
130-3200G 8-8787400x710405055--241048243269303 
130-3200J 8-8787400x710405055--241048243269327 
130-3400F6-6787400x770556575--313048243269358
130-3400J6-6787400x770556575--313048243269372
130-3600E6-6767400x790556575--348048243269402
130-3600J6-6767400x790556575--348048243269426
130-3800E4-4767470x950708595100486048243269457
130-3800J4-4767470x950708595100486048243269471
130-4000E4-4747470x1030708595100533048243269501
130-4000J4-4747470x1030708595100533048243269525
130-4200J3-3757500x104085100110110588048243269570
130-4400J3-3737500x105085100110110647048243269624
130-4600J2-2747565x110095115130125721048243269679
 130-4800J 2-2 727565x120095115 130 125802048243269723 

 130-6000J 

 2/0-2/0 192/019900x1400145175 195 2001412048243269907 
            

 * Per Table 310-16 NEC®
** For termination to equipment for circuits rated 100 amperes or less or marked for 14 AWG through 1 AWG conductors.
*** For termination to equipment for circuits rated over 100 amperes or marked for conductors larger than 1 AWG.
**** Dry locations.
***** For dwelling units, conductors shall be permitted at listed ampacities for 120/240 volt, 3-wire, single-phase service conductors that supply the total load. Per Table 310-15 (B)(6) NEC®.

 

     
Package CodeEFGJ
AWG Size150' Coil200' Coil250' Coil500' Reel
     
8-8-8 Stranded   XX
6-6-8 Stranded X X
6-6-6 StrandedX  X
4-4-6 StrandedX  X
4-4-4 StrandedX  X
3-3-5 Stranded   X
3-3-3 Stranded   X
2-2-4 Stranded   X
2-2-2 Stranded    X
2/0-2/0-2/0 Stranded    X