Triplex 600v

Triplex 600V

DOWNLOAD TRIPLEX 600V GUIDE
 

Applications Top of Page


For use in electrical distribution circuits not exceeding 600 volts phase-to-phase. Cables may be directly buried or installed in ducts. May be used in wet or dry locations at conductor temperatures not exceeding 90°C for normal operation, 130°C for emergency overloads, and 250°C under short-circuit conditions. 

Conductors Top of Page

Hard-drawn stranded, compressed 1350 aluminum per ASTM-B230 and B901 

Conductor Insulation Top of Page


Phase Conductors: Black cross-linked polyethylene
Neutral Conductor: Black cross-linked polyethylene with three continuous extruded
yellow stripes 120° apart. 

Assembly Top of Page

Phase and neutral conductors are twisted together with a left-hand lay not greater than 60 times the outside diameter of one phase conductor.

Industry Standards Top of Page

ASTM-B230
ASTM B901
ANSI/ICEA S-105-692
UL 854 Service Entrance Cables

Surface Print Top of Page

Sample: 4/0 AWG AL XLPE 600V USE-2/YEAR
 

Triplex 600V Secondary UD Aluminum

          


Product Code Word/Number
Phase ConductorsNeutral
Approx. Cable O.D.
Mils.


Approx. Net. Wt. lbs./M ft.


Ampacity for Direct Burial*



Ampacity in Ducts




UPC Code
AWG SizeInsulation ThicknessAWG SizeInsulation Thickness
          
ERSKINE
538-3600K
6606606501339575662927596952
VASSER
538-4000K
46046075019112593662927596006
STEPHENS 538-4800J260460840248165123662927598550
STEPHENS 538-4800K260460840248165123662927596051
RAMAPO
538-5000J
260260870277165123662927596082
SWEETBRIAR
538-6800J
4/0802/0801360705315247662927598758
SWEETBRIAR 538-6800K4/0802/0801360705315247662927598765
MONMOUTH 538-7000J4/0804/0801420792315247662927598802
          

Quadruplex 600V Secondary UD Aluminum

DYKE
539-4800J9
260460940341154104662927598857