UF-B

UF-B                          

DOWNLOAD UF-B PDF

 

Applications Top of Page

 

For use underground as a feeder or branch circuit cable where provided with
overcurrent protection of the rated ampacity as specified by the NEC®. Direct burial in the earth is
permitted. May be installed as interior wiring in wet, dry, or corrosive locations as specified by the
NEC® May be installed as nonmetallic-sheathed cable as specified in NEC® Section 340.10(4). May
be installed in locations with temperatures up to 90°C but with the ampacity limited to that of 60°

Conductors Top of Page

Solid conductors: Soft, uncoated copper per ASTM-B3
Stranded conductors: Uncoated copper per ASTM-B3 and ASTM-B

Conductor Insulation and Jacket Top of Page

 

Color-coded PVC (polyvinyl chloride), rated 90°C dry
Insulated conductors also jacketed with clear nylon (polyamide)

Grounding Conductor Top of Page

Soft, uncoated copper per ASTM-B3

Assembly Top of Page

Insulated conductors are laid parallel with a bare grounding conductor

Jacket Top of Page

A gray, sunlight-resistant PVC (polyvinyl chloride) is applied directly over and around the insulated and bare conductors

Industry Standards Top of Page

UL 83 (insulated conductors) File No. E15119
UL 493 Thermoplastic-Insulated Underground Feeder and Branch Circuit Cables -File No. E26403
ASTM-B3
ASTM-B8
Federal Specification A-A-59544
NFPA70: National Electrical Code®
RoHS Compliant

*It is the sole responsibility of the end user to determine suitability of this product for its intended end use and application.

Surface Print Top of Page

 

Sample: UF-B SUN-RES 12-2 W/G CIRTUF-A (UL) 600V