Triplex 600V

Triplex 600V

Aluminum

Where To BuySpec Sheet PDF
Applications

For use in electrical distribution circuits not exceeding 600 volts phase-to-phase. Cables may be directly buried or installed in ducts. May be used in wet or dry locations at conductor temperatures not exceeding 90°C for normal operation, 130°C for emergency overloads, and 250°C under short-circuit conditions.

  • direct burial
  • wet or dry locations
Conductors

Hard-drawn stranded, compressed 1350 aluminum per ASTM-B230 and B901

Insulation

Phase Conductors

  • Black cross-linked polyethylene

Neutral Conductor

  • Black cross-linked polyethylene with three continuous extruded yellow stripes 120° apart
Industry Standards

ASTM-B230
ASTM B901
ANSI/ICEA S-105-692
UL 854 Service Entrance Cables

Assembly

Phase and neutral conductors are twisted together with a left-hand lay not greater than 60 times the outside diameter of one phase conductor.

Surface Print

Sample: 4/0 AWG AL XLPE 600V USE-2/YEAR