Wire Size Selection for Long Runs
110 Volt, Single Phase, Max 3% Voltage Drop* | |||||||||||
Length of Run | |||||||||||
25' | 50' | 100' | 150' | 200' | |||||||
Copper | 14 | 12 | 8 | 6 | 6 | 15 AMP | |||||
Copper | 12 | 10 | 8 | 6 | 4 | 20 AMP | |||||
Copper | 10 | 8 | 6 | 4 | 3 | 30 AMP | |||||
Copper | 3** | 3** | 1 | 2/0 | 3/0 | 100 AMP | |||||
Aluminum | 2 | 2 | 2/0 | 4/0 | 300 MCM | 100 AMP | |||||
Copper | 3/0 | 3/0 | 3/0 | 250 MCM | 350 MCM | 200 AMP | |||||
Aluminum | 4/0 | 4/0 | 300 MCM | 400 MCM | 600 MCM | 200 AMP | |||||
220 Volt, Single Phase, Max 3% Voltage Drop* | |||||||||
Length of Run | |||||||||
25' | 50' | 100' | 150' | 200' | |||||
Copper | 14 | 14 | 12 | 10 | 8 | 15 AMP | |||
Copper | 12 | 12 | 10 | 8 | 8 | 20 AMP | |||
Copper | 10 | 10 | 8 | 6 | 6 | 30 AMP | |||
Aluminum | 8 | 8 | 6 | 4 | 4 | 30 AMP | |||
Copper | 8 | 8 | 8 | 6 | 4 | 40 AMP | |||
Aluminum | 8 | 8 | 6 | 4 | 3 | 40 AMP | |||
Copper | 8*** | 8*** | 6 | 4 | 4 | 50 AMP | |||
Aluminum | 6 | 6 | 4 | 3 | 2 | 50 AMP | |||
WARNING! Installation of electrical wire can be hazardous, if done improperly, can result in personal injury or property damage. For safe wiring practices, consult the National Electrical Code® and your local building inspector. | |||||||||||||||||